Daitsu WC5/WC6 controller error codes

All seven tables from the official manual, 311 codes, keeping ducted Atlas apart from VRF. Because they are not the same.

First things first: the same code does not mean the same in Atlas and in VRF

The Daitsu ACCD WC5/WC6 controller is fitted both on ducted Atlas systems and on VRF, and the display shows exactly the same reading. But the manufacturer's tables are different: a code that points to one fault on Atlas points to something else on VRF.

And there is a second trap: not every reading is a fault. The manual separates error codes from debugging and status codes, which are the unit telling you what it is doing. Here they are in separate tables, as in the manual, and not all thrown together.

If you do not know which system you have, look at the outdoor unit: if a single outdoor unit feeds several indoor units around the house, it is VRF. If it is one outdoor unit with a single ducted indoor unit in the ceiling void, it is Atlas.

Atlas · outdoor unit · 62

The unit outside, on a ducted system.

CodeWhat the official manual says
A1Outdoor Fan IPM Module Protection
A2ODU Refrigerant Heater Relay Adhesion Error
A3ODU Refrigerant Heater Failure
A4Refrigerant Temperature Sensor Error
A5Outdoor Condenser Inlet Pipe Temperature Sensor Error
A7Outdoor Condenser Outlet Pipe Temperature Sensor Error
AcOutdoor Fan Startup Failure
AdOutdoor Fan Out-ofphase Protection
AEOutdoor Fan Current Detecting Circuit Error
AJOutdoor Fan Nonsynchronism Protection
b5Liquid Valve Temperature Sensor Error
b7Gas Valve Temperature Sensor Error
C3Outdoor Condenser Middle Pipe Temperature Sensor Error
C4ODU Jumper Cap Error
C6Discharge Temperature Sensor Error
C7Outdoor Pipe Middle Sensor Error
C8Compressor DIP Switch/ Jumper Cap Error
C9Compressor Drive Storage Chip Error
CdAbnormal Electrical Level of Selected Port
dcCompressor Suction Temperature Sensor Error
dJAC Phase Sequence Protection (phase loss or phase reversal)
E1System High Pressure Protection
E2Freeze Protection
E3System Low Pressure Protection
E4Discharge Protection
E6Communication Error between ODU and IDU
ELEmergency Operation Stop
F3Outdoor Ambient Temperature Sensor Error
H4Overload Protection
H5Module Current Protection
H7Compressor Non-synchronism
HCPFC Overcurrent Error
HECompressor Demagnetization Protection
L3Outdoor Fan 1 Error
L9High Power Protection
LAOutdoor Fan 2 Error
LcStartup Failure
LECompressor Stalling
LFOverspeed
oEOther Error of Compressor
P0Drive Module Reset
P5Overcurrent of Compressor Phase Current
P6Drive Board Communication Error
P7Module Temperature Sensor Circuit Error
P8Module Temperature Protection
P9AC Contactor Protection
PAODU AC Current Protection
PdSensor Connection Protection (current sensor hasn’t been connected to corresponding U phase or V phase)
PETemperature Shifting Protection
PFDrive Board Ambient Temperature Sensor Error
PHHigh Voltage Protection of DC Bus
PLLow Voltage Protection of DC Bus
PPDC Input Voltage Error
PUCapacitor Charging Error
U1Compressor Phase Current Circuit Detecting Error
U2Compressor Phase Loss/ Phase Reversal/Out of Phase
U3DC Bus Voltage Drop Error
U5Current Detecting Error of Complete Unit
U74-way Valve Commutation Error
U8Zero-crossing Signal Error
ULOutdoor Fan Overcurrent Protection
UoAbnormal Outdoor Ambient Temperature (heating at too high ambient temperature or cooling at too low ambient temperature)

Atlas · indoor unit · 39

The one in the ceiling void. Usually sensors, drainage or communication with the controller.

CodeWhat the official manual says
C0Communication Error between Indoor Unit and Wired Controller
C1Indoor Ambient Temperature Sensor Error
C2Indoor Evaporator Middle Temperature Sensor Error
CEWired Controller Temperature Sensor Error
CJIDU Jumper Cap Error
CPMultiple Master Wired Controllers Error
dHWired Controller Circuit Board Error
E0Indoor Fan Error
E3Refrigerant Lacking Protection
E7Mode Conflict
E9IDU Water Full Protection
EEMemory Chip Read and Write Error
L1Indoor Humidity Sensor Error
L4Wired Controller Power Supply Circuit Failure
L5Wired Controller Power Supply Overcurrent Protection
L6Group-controlled IDU Quantity Inconsistency
L7Group-controlled IDU Series Inconsistency
LbGroup-controlled IDU Inconsistency of Reheat Dehumidification System
LPMismatch of IDU and ODU Models
q0Low Voltage Protection or Voltage Drop Error of Inverter Indoor Fan Drive DC Bus
q1High Voltage Protection of Inverter Indoor Fan Drive DC Bus
q2Inverter Indoor Fan AC Current Protection (input side)
q3Inverter Indoor Fan Drive IPM Module Protection
q4Inverter Indoor Fan Drive PFC Protection
q5Inverter Indoor Fan Startup Failure
q6Inverter Indoor Fan Outof-phase Protection
q7Inverter Indoor Fan Drive Module Reset
q8Inverter Indoor Fan Overcurrent Protection
q9Inverter Indoor Fan Power Protection
qAInverter Indoor Fan Drive Current Detecting Circuit Error
qbInverter Indoor Fan Nonsynchronism Protection
qCMain Control and Inverter Indoor Fan Drive Communication Error
qdInverter Indoor Fan Drive Module High Temperature Protection
qEInverter Indoor Fan Drive Module Temperature Sensor Error
qFInverter Indoor Fan Drive Storage Chip Error
qHInverter Indoor Fan Drive Charging Circuit Error
qLInverter Indoor Fan Drive AC Input Voltage Abnormal Protection
qoInverter Indoor Fan Drive Electric Box Temperature Sensor Error
qpInverter Indoor Fan Drive AC Input Zero-crossing Protection

Atlas · status codes · 6

Not faults: the unit telling you what it is doing.

CodeWhat the official manual says
CLAuto clean
d1DRED operation mode 1
d2DRED operation mode 2
d3DRED operation mode 3
FoRefrigerant recycle mode
H1Ordinary defrosting status

VRF · outdoor unit · 71

On VRF a single outdoor unit feeds several indoor units, so a fault here takes the whole installation out of service.

CodeWhat the official manual says
b1Outdoor Ambient Temperature Sensor Error
b2Defrosting Temperature Sensor 1 Error
b3Defrosting Temperature Sensor 2 Error
b4Subcooler Liquid-out Temperature Sensor Error
b5Subcooler Gas-out Temperature Sensor Error
b6Gas-liquid Separator Inlet Temperature Sensor Error
b7Gas-liquid Separator Outlet Temperature Sensor Error
b8Outdoor Humidity Sensor Error
b9Heat Exchanger Gas-out Temperature Sensor Error
bAOil-return Temperature Sensor Error
bbOil-return 4 Temperature Sensor Error
bdAir-in Temperature Sensor Error of Subcooler
bEMalfunction of Entry Tube Temperature Sensor of Condenser
bFMalfunction of Exit Tube Temperature Sensor of Condenser
bHSystem Clock Malfunction
bJHigh and Low Pressure Sensors are Connected Inversely
bnLiquid-in Temperature Sensor Error of Subcooler
bPOil-return 2 Temperature Sensor Error
bUOil-return 3 Temperature Sensor Error
byWater-out Temperature Sensor Error
E0Outdoor Unit Error
E1High Pressure Protection
E2Discharge Low Temperature Protection
E3Low Pressure Protection
E4Excess Discharge Temperature Protection of Compressor
EdLow Temperature Protection of Driver Module
F0Bad Performance of the Outdoor Mainboard
F1High Pressure Sensor Error
F2Inlet Tube Temperature Sensor Error of Plate Type Heat Exchanger
F3Low Pressure Sensor Error
F4Outlet Tube Temperature Sensor Error of Plate Type Heat Exchanger
F5Compressor 1 Discharge Temperature Sensor Error
F6Compressor 2 Discharge Temperature Sensor Error
F7Compressor 3 Discharge Temperature Sensor Error
F8Compressor 4 Discharge Temperature Sensor Error
F9Compressor 5 Discharge Temperature Sensor Error
FACompressor 6 Discharge Temperature Sensor Error
FbCompressor 2 Top Temperature Sensor Error
FCCompressor 2 Current Sensor Error
FdMode Exchanger Outlet Pipe Temperature Sensor Error
FECompressor 4 Current Sensor Error
FFCompressor 5 Current Sensor Error
FJCompressor 6 Current Sensor Error
FLCompressor 3 Current Sensor Error
FnMode Exchanger Inlet Pipe Temperature Sensor Error
FPMalfunction of DC motor
FUCompressor 1 Top Temperature Sensor Error
FyWater-in Temperature Sensor Error
GHPV DC/DC Protection
H0Error of Fan Drive Board
H1Malfunction of Fan Drive Board
H2Protection of Fan Drive Board Power Supply
J1Compressor 1 Over-current Protection
J2Compressor 2 Over-current Protection
J3Compressor 3 Over-current Protection
J4Compressor 4 Over-current Protection
J5Compressor 5 Over-current Protection
J6Compressor 6 Over-current Protection
J74-way Valve Blow-by Protection
J8System Pressure Over-Ratio Protection
J9System Pressure UnderRatio Protection
JAProtection of Abnormal Pressure
JCProtection of Water Flow Switch
JEOil Return Pipe is Blocked
JFOil Return Pipe is Leaking
JJLow Water-in Temperature Protection
JLProtection of Low Highpressure
P0Compressor Drive Board Error
P1Compressor Drive Board Malfunction
P2Protection of Compressor Drive Board Power Supply
P3Protection of Compressor Drive Board Module Reset

VRF · indoor unit · 61

Each of the units around the house.

CodeWhat the official manual says
d1Indoor Unit PC-Board Error
d3Ambient Temperature Sensor Error
d4Inlet Pipe Temperature Sensor Error
d5Malfunction of Middle Tube Temperature Sensor
d6Outlet Pipe Temperature Sensor Error
d7Humidity Sensor Error
d8Water Temperature Abnormality
d9Jumper Cap Error
dAIndoor Unit Hardware Address Error
dbSpecial Code: Field Debugging Code
dCCapacity DIP Switch Setting Error
dEIndoor Unit CO Sensor Error 2
dHWired Controller PC-Board Error
dLOutlet Air Temperature Sensor Error
dnSwing Assembly Error
dyWater Temperature Sensor Error
L0Indoor Unit Error
L1Indoor Fan Protection
L2E-heater Protection
L3Water Full Protection
L4Wired Controller Power Supply Error
L5Anti-Frosting Protection
L6Mode Conflict
L7No Master Indoor Unit Error
L8Power Insufficiency Protection
L9Quantity Of Group Control Indoor Units Setting Error
LAIndoor Units Incompatibility Error
LbInconsistency of Groupcontrolled Indoor Units in Reheat Dehumidification System
LCOutdoor-Indoor Incompatibility Error
LdIndoor Fan 2 Error
LFShunt Valve Setting Error
LHLow Air Quanlity Warning
LJWrong Setting of Function DIP Switch
LnLift Panel Return Air Frame Reset Exception
LPZero-crossing Malfunction of PG Motor
LUInconsistent Branch of Group-controlled Indoor Units in Heat Recovery System
o0Motor Drive Error
o1Low Voltage of IDU Bus Bar
o2High Voltage of IDU Bus Bar
o3IDU IPM Module Protection
o4IDU Startup Failure
o5IDU Overcurrent Protection
o6IDU Current Detective Electric Circuit Error
o7IDU Losing Step Protection
o8IDU Driver Communication Error
o9Communication Error of IDU Master Controller
oAHigh Temperature of IDU Module
obTemperature Sensor Error of IDU Module
oCIDU Charging Circuit Error
y1Inlet Pipe Temperature Sensor 2 Error
y2Outlet Pipe Temperature Sensor 2 Error
y3Middle Tube Temperature Sensor 2 Error
y7Fresh Air Inflow Temperature Sensor Error
y8Indoor Air Box Sensor Error
y9Outdoor Air Box Sensor Error
yAIFD error
yCAir-return Inlet Sensor Error
yEHigh Liquid Level Switch Error
yFLow Liquid Level Switch Error
yHFresh Air-out Sensor Error
yLAir-return Outlet Temperature Sensor Error

VRF · debugging codes · 41

These show up during commissioning and setting up. If you see one in normal use, somebody left the installation half configured.

CodeWhat the official manual says
C0Communication between indoor unit and outdoor unit and the communication between indoor unit and wired controller have malfunction
C1Communication error of expansion board
C2Communication error between master control and inverter compressor drive
C3Communication error between master control and inverter fan motor drive
C4Error of Lack of Indoor Unit
C5Alarm of Indoor Unit Project Number Collision
C6Alarm of Wrong Number of Outdoor Unit
C7Mode Exchanger Communication Error
CbOutflow of Units IP Address
CCNo master control unit error
CdCommunication Failure Between Mode Exchanger and Outdoor Unit
CECommunication Failure Between Mode Exchanger and Indoor Unit
CFError of Multiple Master Indoor Unit
CHRated capacity is too high
CJSystem addresses is incompatible
CLRated capacity is too low
CnIndoor and Outdoor Network Error of Mode Exchanger
CPError of Multiple Master Wired Controller
CUCommunication Error between Indoor Unit and Remote Receiver
CyCommunication Error of No Master in Mode Exchanger
U2Outdoor Unit Capacity Code/Jumper Cap Setting Error
U3Phase Sequence Protection of Power Supply
U4Protection of Lack of Refrigerant
U5Wrong Address of Compressor Drive Board
U6Valve Abnormal Alarm
U7Grid DRED0 Response Protection
U8Indoor Unit Tube Malfunction
U9Outdoor Unit Tube Malfunction
UAOvervoltage Protection of DC Bus Bar in Power Grid Side
UbProtection without shutdown error of thermal storage module
UCMaster indoor unit is successfully set
UdGrid-connection driver board error
UERefrigerant Charging is ineffective
UFIndoor Unit Identification Error of Mode Exchanger
UHUnder voltage Protection of DC Bus Bar in Power Grid Side
UJPV module F0 protection
ULEmergency Operation DIP switch setting of the compressor is wrong
UnCommunication error between grid-connection driver board and master controller
UPProtection shutdown error of thermal storage module
UUElectronic expansion valve leak error of thermal storage module
UyPV module overheating protection

VRF · status codes · 31

Not faults either.

CodeWhat the official manual says
A0Unit is waiting for debugging
A1Check the compressor operation parameters
A2After-sales Refrigerant Reclaim
A3Defrosting
A4Oil return
A5Online Testing
A8Vacuum-pumping Mode
A9Operate in Setback Function
AbEmergency Stop
ACCooling
AdOperation Restriction
AFFan
AHHeating
AJFilter Clean Reminder
AnLock status
AURemote Urgent Stop
AyShielding status
n3Compulsory defrosting
q5Setting of ordinary units and high sensible heat units
q7Select degree Celsius or Fahrenheit
q8Discharge low temperature protection revision value b
q9Setting of defrosting mode
qbAnti-condensation temperature setting
qdSetting of target degree of super-cooling of ODU
qEEVI Operating Mode
qFSystem compulsory cooling mode
qLSetting of static pressure
qnPV grid-connected settings
qPPV GMV Unit export area setting
qUGrid voltage system configuration
qyWorking mode of compressor heating belt

Frequently asked questions

Frequently asked questions about Daitsu WC5/WC6 error codes

Does the same code mean the same on an Atlas and on a VRF?

No, and it is the most expensive mix-up in this range. The Daitsu WC5/WC6 controller is fitted both on ducted Atlas systems and on VRF, but the code tables are different: the same reading points to one fault on one system and to something else on the other. Before looking at any table you need to know which system you have.

Are all these codes faults?

No, and this misleads a lot of people. The manual separates error codes from debugging and status codes. Status codes are the unit telling you what it is doing; debugging codes come up during commissioning. Seeing one and assuming the unit is broken is a scare for nothing, which is why they are in separate tables here.

Where do these codes come from?

From the manufacturer's official manual, UM-ACCD-WC5-WC6 (11/22 edition), section 6. They are extracted from the PDF and published in the manufacturer's own wording: not copied from another website and not written from memory.

A code has come up, is there anything I can do myself?

You can note it down, check whether the filter is dirty, whether there is water in the tray or whether something has tripped in the consumer unit, and restart. What makes no sense is resetting over and over: if the unit is protecting itself, it is doing so for a reason, and forcing it costs more than the call-out.

Do you work with Daitsu across Mallorca?

Yes. We install and repair Daitsu across the island, both ducted and VRF, and we assist you in English, Spanish and German. If you have the code on screen, tell us when you call: it saves a visit.